Comparative DGA-Based Fault Diagnosis and Root-Cause Assessment of Transformer using Duval Triangle and Pentagon Graphical Method

This study utilizes real-world Dissolved Gas Analysis (DGA) data from a failed power transformer in a hot climate to demonstrate that the Duval Triangle and Pentagon graphical methods offer superior diagnostic accuracy and root-cause clarity compared to traditional ratio-based techniques like Rogers Ratio and IEC 60599 for identifying mixed electrical and thermal insulation faults.

Original authors: Varsha Thakur, Chilaka Ranga

Published 2026-11-26
📖 1 min read☕ Coffee break read

Original authors: Varsha Thakur, Chilaka Ranga

Original paper licensed under CC BY 4.0 (https://creativecommons.org/licenses/by/4.0/). ✨ This is an AI-generated explanation of the paper below. It is not written or endorsed by the authors. For technical accuracy, refer to the original paper. Read full disclaimer

Technical Summary: Comparative DGA-Based Fault Diagnosis and Root-Cause Assessment of Transformer using Duval Triangle and Pentagon Graphical Method

Problem Statement
Power transformers are critical assets in electrical grids, yet their reliability is frequently compromised by the degradation of liquid and solid insulation systems. This degradation, accelerated by thermal stress, electrical stress, and chemical oxidation, leads to the generation of dissolved gases within the transformer oil. While Dissolved Gas Analysis (DGA) is the standard technique for diagnosing incipient faults, traditional ratio-based methods (such as Rogers Ratio, Doernenburg Ratio, and IEC 60599) often suffer from diagnostic ambiguity. These ambiguities arise from overlapping fault boundaries and inconsistent interpretations under similar operating conditions, making it difficult to precisely distinguish between high-temperature thermal faults (T3), high-energy discharges (D2), and low-energy discharges (D1).

Methodology
This study presents a comparative analysis of various DGA interpretation techniques applied to real-world failure data. The dataset consists of oil samples collected from failed power transformers operated by the Chhattisgarh State Electricity Board (CSEB) under hot-climate conditions, where high ambient temperatures accelerated thermal aging.

The methodology involved the following steps:

  1. Data Collection: Real-time DGA data was obtained from transformers that experienced abnormal gas generation due to thermal stress, overloading, and insulation degradation.
  2. Comparative Analysis: The study evaluated the performance of four diagnostic approaches:
    • Doernenburg Ratio Method (DRM): Utilizing four gas concentration ratios (R1–R4) to classify faults.
    • Rogers Ratio Method (RRM): Using three gas ratios (R1–R3) based on IEC standards.
    • IEC 60599 Standard: A modified ratio-based approach for thermal fault diagnosis.
    • Graphical Methods: The Duval Triangle (DTM) and the Duval Pentagon.
  3. Graphical Implementation:
    • Duval Triangle: Normalized the concentrations of Acetylene (C2H2C_2H_2), Ethylene (C2H4C_2H_4), and Methane (CH4CH_4) to sum to 100%. These percentages were plotted on a ternary coordinate system to identify fault zones (PD, D1, D2, T1–T3).
    • Duval Pentagon: An advanced extension incorporating Hydrogen (H2H_2) and Ethane (C2H6C_2H_6) alongside the three hydrocarbons. The method calculated the centroid of the polygon formed by the five gas percentages to determine the fault type with higher precision.

Key Results
The analysis of the real failure data yielded the following findings:

  • Limitations of Ratio Methods: The Doernenburg and Rogers ratio methods provided inconsistent or ambiguous results. For instance, the Rogers Ratio method failed to accurately detect incipient faults, and the IEC 60599 standard could not precisely determine fault severity or location in all cases.
  • Effectiveness of Graphical Methods: The Duval Triangle and Pentagon methods demonstrated superior clarity in fault zone separation.
    • Data Point 1: Identified as a D1 (low-energy discharge) fault.
    • Data Point 2: Identified as a D2 (high-energy discharge/arcing) fault, indicating severe insulation destruction and carbonization.
    • Data Point 3: Identified as a T3 (high-temperature thermal) fault, indicating overheating above 700°C.
  • Root Cause Assessment: The results confirmed the presence of both electrical and thermal fault signatures, indicating severe deterioration of the internal insulation system. The study noted that failures were more frequent during hot climate periods (April to June) due to increased thermal stress accelerating insulation aging.

Significance and Claims
The paper claims that the Duval Triangle and Pentagon graphical methods offer a more reliable and precise alternative to conventional ratio-based techniques for post-failure diagnostics. By utilizing normalized gas percentages rather than absolute concentrations or fixed ratios, these graphical approaches reduce diagnostic uncertainty and provide clearer fault-zone separation.

The study emphasizes that:

  1. Accuracy: The Duval Triangle effectively identifies specific fault types (T3, D1, D2) and conditions, facilitating accurate root-cause assessment.
  2. Operational Context: The research highlights the critical impact of hot-climate operating conditions on transformer aging, suggesting that continuous monitoring is essential for predictive maintenance.
  3. Future Direction: While the current study focuses on post-failure analysis, the authors suggest that integrating DGA with temperature and other insulation health indicators could improve early-warning mechanisms. However, the paper does not propose new experimental setups or unverified applications, focusing instead on validating the effectiveness of existing graphical methods using empirical failure data.

In conclusion, the authors assert that adopting advanced graphical methods like the Duval Triangle and Pentagon enhances the effectiveness and efficiency of fault identification, thereby supporting better maintenance planning and operational reliability for power transformers.